Product Description
- The SMC HRS cooling and temperature control unit, in its compact version, is used for cooling and temperature control of circulating media in industrial processes.
- It is suitable for applications where a constant medium temperature is required to ensure process quality.
- The cooling and temperature control unit can be used in production and automation systems with different mains voltages.
- The SMC HRS cooling and temperature control unit is a water-cooled industrial chiller designed for liquid cooling, featuring a compact design.
- The unit offers high temperature stability and uses environmentally friendly refrigerants.
- Standard features include a communication function with RS232C and RS485 interfaces, as well as digital inputs and outputs.
- Filter maintenance requires no tools, and the integrated self-diagnostic function helps to identify faults quickly.
- Cooling method – Water-cooled version
- Refrigerant – R407C (HFC) (up to HRS030) or R410A (HFC) (from HRS040)
- Refrigerant quantity – 0.3 to 0.75 kg
- Control method – PID control
- Ambient temperature: -5 to 40 °C
- Humidity – Relative humidity 30 to 70 %
- Altitude – Up to 3000 m
- Circulating fluid – tap water, 15% aqueous ethylene glycol solution
- Adjustable temperature range: -5 to 40 °C
- Cooling capacity (50/60 Hz) – 1100/1300 to 4900/5900 W
- Heating power (50/60 Hz) – 400/600 to 1000/1300 W
- Temperature stability – ±0.1 °C
- Nominal pump flow rate (50/60 Hz) – 7 l/min, 0.13 MPa / 7 l/min, 0.18 MPa
- Max. pump flow rate (50/60 Hz) – 27/29 l/min to 29/38 l/min
- Max. delivery head (50/60 Hz) – 14/19 m or 50 m
- Pump power – 200 or 550 W
- Capacity – approx. 5 l
- Connection size – Rc, G or NPT 1/2"
- Materials in contact with the medium – stainless steel, copper (heat exchanger brazing), bronze, aluminium oxide ceramic, carbon, PP, PE, POM, FKM, EPDM, PVC
- Temperature range of the system water – 5 to 40 °C
- Pressure range of the system water – 0.3 to 0.5 MPa
- Required system water flow rate – 8 to 17 l/min
- Inlet/outlet pressure differential of the system water – 0.3 MPa
- System water connection size – Rc 3/8"
- Materials in contact with the medium (system water) – stainless steel, copper solder (heat exchanger), bronze, synthetic rubber
- Power supply – single-phase 200 to 230 V AC (50/60 Hz), permissible voltage range ±10 %
- Short-circuit protection – 10 or 20 A
- Recommended fuse trip current – 10 or 20 A
- Rated operating current (50/60 Hz) – 4.6/5.1 to 7.6/10.4 A
- Rated power consumption (50/60 Hz) – 0.9/1.0 to 1.5/2.1 kVA
- Noise level (50/60 Hz) – 60/61 to 66/68 dB(A)
- Height – 650 to 976 mm
- Width – 377 mm
- Depth – 521 to 592 mm
- Weight – 43 to 67 kg