Product Description
- The SMC HRS cooling and temperature control unit is used for cooling and temperature control of circulating media in industrial processes.
- It is suitable for applications where a constant medium temperature is required for machines, systems or heat sources.
- The unit is used in automated production and manufacturing environments to stabilise process conditions.
- It is designed for use as an industrial cooler in liquid cooling circuits.
- The SMC HRS cooling and temperature control unit is a compact industrial cooler for liquid cooling, featuring an air-cooled design.
- The temperature is precisely controlled via a PID control system, ensuring high temperature stability.
- The unit features self-diagnostic, alarm and monitoring functions with numerous alarm codes.
- Serial communication interfaces, as well as inputs and outputs, enable connection to higher-level control systems.
- Cooling method – Air-cooled version
- Refrigerant – R407C (HFC) (up to HRS030) or R410A (HFC) (from HRS040)
- Refrigerant charge – 0.35 to 0.85 kg
- Control method – PID control
- Ambient temperature: -5 to 40 °C
- Humidity – Relative humidity 30 to 70 %
- Altitude – Up to 3000 m
- Circulating fluid – tap water, 15% aqueous ethylene glycol solution
- Adjustable temperature range: -5 to 40 °C
- Cooling capacity (50/60 Hz) – 1100/1300 to 4900/5900 W
- Heating power (50/60 Hz) – 360/450 to 1000/1300 W
- Temperature stability – ±0.1 °C
- Nominal pump flow rate (50/60 Hz) – 7 l/min, 0.13 MPa / 7 l/min, 0.18 MPa
- Max. pump flow rate (50/60 Hz) – 27/29 l/min to 29/42 l/min
- Max. delivery head (50/60 Hz) – 14/19 m or 50 m
- Pump power – 200 or 550 W
- Capacity – approx. 5 l
- Connection size – Rc or G 1/2"
- Materials in contact with the medium – stainless steel, copper (heat exchanger brazing), bronze, aluminium oxide ceramic, carbon, PP, PE, POM, FKM, EPDM, PVC
- Power supply – single-phase 200 to 230 VAC (50/60 Hz), permissible voltage range ±10 %
- Short-circuit protection – 10 to 30 A
- Recommended fuse trip current – 10 to 30 A
- Rated operating current (50/60 Hz) – 4.6/5.1 to 8.9/11.5 A
- Rated power consumption (50/60 Hz) – 0.9/1.0 to 1.8/2.3 kVA
- Noise level (50/60 Hz) – 60/61 to 66/68 dB(A)
- Height – 650 to 976 mm
- Width – 377 mm
- Depth – 521 to 592 mm
- Weight – 43 to 73 kg